NOTE: In the psychrometric chart the abscissa is the operative temperature and for each point dry-bulb temperature equals mean radiant temperature (DBT = MRT). The comfort zone represents the combination of conditions with the same DBT and MRT for which the PMV is between -0.5 and +0.5, including the ASHRAE 55 Appendix H cooling effect of elevated air speed. Chart legend: t_db = dry-bulb temperature, t_dp = dew point, t_wb = wet-bulb.
Limits of Applicability: This standard is only applicable to healthy individuals. This standard does not apply to occupants: a) whose clothing insulation exceed 1.5 clo; b) whose clothing is highly impermeable; or c) who are sleeping, reclining in contact with bedding, or able to adjust blankets or bedding.
The tool applies the ASHRAE 55-2023 relative-air-speed and dynamic-clothing corrections before evaluating PMV, and the Appendix H cooling effect (via SET) for elevated air speed.
NOTE: In this psychrometric chart the abscissa is the dry-bulb temperature and the mean radiant temperature (MRT) is fixed. Each band marks the EN-16798 comfort categories I, II and III.
EN-16798 (ISO 7730) mode uses the raw air speed and clothing inputs: the ASHRAE 55-2023 relative-air-speed and dynamic-clothing corrections are not applied. In adaptive mode the comfort temperature is 0.33 × running mean + 18.8 °C with category I/II/III bands per EN 16798-1:2019, plus the elevated-air-speed cooling effect.
NOTE: The green zone marks the conditions of inputs #1 where PMV is between -0.5 and +0.5 (ASHRAE 55-2023, with relative-air-speed and dynamic-clothing corrections). The red dot is condition #1 and the blue dot is condition #2.
Chart legend: t_db = dry-bulb temperature, t_dp = dew point, t_wb = wet-bulb, W_a = humidity ratio, h = enthalpy. The chart shows humidity ratio vs. operative temperature.
Outer range of air temperatures: 4.1 °C
Given the other four parameters, occupants will find thermal comfort in the wider range of temperatures shown, as long as the varied parameter can change within the given range.
Inner range of air temperatures: 1.8 °C
Given the other four parameters, this is the range of temperatures in which all the occupants will find thermal comfort for every value of the varied parameter selected above. The inner range is zero if the comfort zones corresponding to the first and last conditions do not intersect.
Chart legend: t_db = dry-bulb temperature, t_dp = dew point, t_wb = wet-bulb, W_a = humidity ratio, h = enthalpy. Each green zone is drawn vs. the operative temperature.
Calculate comfort indexes in batch
Uploading datasets is handled by the Analyse my data workbench in this application: it reads CSV files and computes comfort indexes (PMV, PPD, SET, cooling effect) with the same pythermalcomfort model family used here.
Single-condition and two-condition evaluation are available on the ASHRAE-55, EN-16798 and Compare tabs of this tool; parameter sweeps are on the Ranges tab.