Inputs
°C
m/s
%
met
clo
Atmospheric pressure: kPa
✔ Complies with ASHRAE Standard 55-2023
PMV = -0.16 PPD = 6 % Sensation = Neutral SET = 24.8 °C

NOTE: In the psychrometric chart the abscissa is the operative temperature and for each point dry-bulb temperature equals mean radiant temperature (DBT = MRT). The comfort zone represents the combination of conditions with the same DBT and MRT for which the PMV is between -0.5 and +0.5, including the ASHRAE 55 Appendix H cooling effect of elevated air speed. Chart legend: t_db = dry-bulb temperature, t_dp = dew point, t_wb = wet-bulb.

Limits of Applicability: This standard is only applicable to healthy individuals. This standard does not apply to occupants: a) whose clothing insulation exceed 1.5 clo; b) whose clothing is highly impermeable; or c) who are sleeping, reclining in contact with bedding, or able to adjust blankets or bedding.

The tool applies the ASHRAE 55-2023 relative-air-speed and dynamic-clothing corrections before evaluating PMV, and the Appendix H cooling effect (via SET) for elevated air speed.