Metadata-Version: 2.4
Name: siemenslib
Version: 0.1.0
Summary: Read what DIGSI writes into an SCL file beside the standard: SIPROTEC product codes, application templates and GOOSE applications
Author: Guilherme Marini
License-Expression: AGPL-3.0-or-later
Project-URL: Homepage, https://github.com/GuilhermeMarini/Siemenslib
Project-URL: Source, https://github.com/GuilhermeMarini/Siemenslib
Keywords: siemens,siprotec,digsi,scl,scd,iec61850,goose,protection,relay,commissioning
Classifier: Development Status :: 3 - Alpha
Classifier: Intended Audience :: Manufacturing
Classifier: Programming Language :: Python :: 3
Classifier: Programming Language :: Python :: 3.10
Classifier: Programming Language :: Python :: 3.11
Classifier: Programming Language :: Python :: 3.12
Classifier: Programming Language :: Python :: 3.13
Classifier: Programming Language :: Python :: 3.14
Classifier: Topic :: Scientific/Engineering
Requires-Python: >=3.10
Description-Content-Type: text/markdown
License-File: LICENSE
Provides-Extra: dev
Requires-Dist: pytest>=8.0; extra == "dev"
Requires-Dist: ruff>=0.6; extra == "dev"
Requires-Dist: mypy>=1.11; extra == "dev"
Dynamic: license-file

# Siemenslib

Read what DIGSI writes into an SCL file **beside** the standard.

```bash
pip install siemenslib
```

```python
from pathlib import Path
from siemenslib import digsi

scd = Path("station.scd")

for ied in digsi.read_ieds(scd):
    print(ied.name, ied.device, ied.digsi_name, ied.application_template)
# QPC2_TR1_AL11 7SJ85 AL11_UPC1 7SJ85_Non_Directional_OC
# QPC1_TR1_UPC1 7UT85 TR1_UPC1  7UT8x_2WindTransformer_Basic

for app in digsi.read_goose_applications(scd):
    print(app.name, app.app_id, app.ied_names)
# 138 kV  0001 ['QPC1_LT1_UPC1', 'QPC1_LT2_UPC1', ...]
# 34,5 kV 0002 ['QPC2_TR1_AL11', 'QPC2_TR1_AL12', ...]
```

| module | what it reads |
|---|---|
| `siemenslib.digsi` | the `Siemens-*` privates and the `siedig` namespace in an SCD/ICD: SIPROTEC product codes, application templates, DIGSI names and revisions, and the GOOSE applications |

## Why this exists

An SCD from the Siemens IEC 61850 System Configurator is ordinary SCL with a
second layer folded into it. The reference station — 14 IEDs — carries **2,473**
`<Private type="Siemens-*">` elements, and no vendor-neutral reader looks at
one of them. They hold what a commissioning engineer actually asks about a
SIPROTEC: which device it is, which application template it was built from,
what DIGSI calls it, and when it last changed.

The GOOSE applications are the part that earns the library. DIGSI groups
datasets into named applications — "138 kV", "34,5 kV" — and the grouping is
by GUID:

```xml
<siedig:GooseApplication name="138 kV">
    <siedig:DataSet guidRef="1f741f02..." />        <!-- an opaque hex string -->

<IED name="QPC1_TR1_UPC1"> … <LN0> <DataSet>
    <Private type="Siemens-GUID">1f741f02...</Private>    <!-- lives over here -->
```

Walking that link turns a list of hex strings into the IEDs that publish in
each application. On the reference station all 14 datasets resolve, and the two
applications split cleanly by voltage level.

## What this does not do

**It does not read the standard half of IEC 61850.** An SCD's IEDs, GOOSE
control blocks, addressing and data model are ordinary SCL, and
[SELlib](https://github.com/GuilhermeMarini/sellib)'s `scl` module reads them
for any vendor — the reference station parses with it unchanged. A second
reader for one standard format would be two things to keep right instead of
one. This library is for what is Siemens' *own*.

**It does not write.** Reading is what a commissioning job needs from these
privates; nothing here modifies a project DIGSI owns.

## Status

Alpha, and proven against one real station: 14 IEDs, 2 GOOSE applications,
read in 324 ms.

## Licence

AGPL-3.0-or-later.