This is a generated example for a fictional college. The meter readings, future sample dates and tariff are invented. The figures below are not real customer results or a savings forecast.
Example FE College (synthetic)
Meter 1099999999990 · 2026-09-01 00:00 to 2026-12-01 00:00 UK time · from college_hh_sample.csv
Read this first
12 half hours missing; totals are not scaled up.
At a glance
Measured consumption
67,732 kWh
Coverage
99.7% of half hours
Peak demand
64.8 kW
Base load (overnight)
18.1 kW
Out-of-hours share
46%
Load factor
0.48
Estimated reads
4.0% of kWh
Cost (excl. VAT, levies)
£17,603.14
What the data says
46% of measured consumption (31,446 kWh) fell outside the declared operating hours (mon-fri 08:00-18:00).
If out-of-hours demand had dropped to the overnight base load, about 4,231 kWh of the measured period would not have been used — an indication of opportunity, not a guaranteed saving.
The overnight base load is 18.1 kW — 28% of the peak demand of 64.8 kW (at 2026-10-21 09:00).
A complete closed day averages 477 kWh against 856 kWh on a working day — 56% (closed = days the declared hours never open, plus listed holidays).
Load factor 0.48 (average ÷ peak demand); a low figure means short, sharp peaks that a capacity charge prices in full.
Day by day
Amber bars are days with missing half hours — their totals are measured only and look lower than the day really was.
When the power is used
Cost by time band
Band
Rate
kWh
Cost
Share of cost
red
38p
8,726
£3,315.93
19%
day
26p
45,876
£11,927.83
68%
night
17p
13,129
£2,231.99
13%
Tariff: Illustrative three-rate (demo only). Unit cost £17,475.74 at an average 25.80p/kWh; standing charge 91 days × 140p = £127.40.
Unit costs cover measured half hours only; missing half hours are not priced, so a bill for the same period will be higher.
Moving use out of the 'red' band (8,726 kWh) to the cheapest rate would save at most £1,832.49 — an upper bound: assumes ALL of this band's use could move to the cheapest rate; in practice only flexible loads can move.
What this report cannot tell you
Measured half hours only — gaps are not filled or scaled up.
Base load = median demand 00:00–05:00 local (912 half hours).
Operating hours are as declared (mon-fri 08:00-18:00), not detected from the data; bank holidays count as closed only when listed.
Out-of-hours consumption above the overnight base load: an indication of opportunity, not a guaranteed saving — some of it may be needed (cleaning, security lighting, frost protection, refrigeration).
A supplier file shows when power was used, not by what. Naming the equipment needs a site visit, sub-metering or the building management system.
The header states no unit; values assumed to be kWh per half hour.
Period columns count half hours from UK local midnight.
Not included in costs: VAT, Climate Change Levy, capacity / availability (kVA) charges, reactive power charges, any separately itemised DUoS / TNUoS / metering charges.
Generated 2026-10-31 08:45 by iaiops from the supplied half-hourly file. Pure analysis of that file: no device or service was contacted.