Requirements
    If possible, left DC buses shall be powered by left generators
    Failed generators must be disconnected within 15 ms
    Generators shall never connect in parallel through AC buses
    When a contactor receives an open signal, it opens in 10ms or less
    When a contactor receives an close signal, it closes in 10ms or less
    A DC bus shall never be unpowered for more than 30ms

Assumptions
    Generators do not recover from failures
    AC buses do not fail
    Rectifiers do not fail
    DC buses do not fail
    Loads do not fail
    At most 1 generator may fail