<p align="center"><img src="https://raw.githubusercontent.com/smartedge-tech-dev/sme-bacnet-sim/main/docs/assets/logo.svg" width="112" alt="SME BACnetSim logo"></p>

<h1 align="center">SME BACnetSim</h1>

<p align="center"><strong>Simulate a building's BACnet devices on your laptop.</strong> Lighting, AC, AHUs, meters, sensors and PV<br>on one UDP port, with a live web UI.</p>

<p align="center"><a href="https://smartedge-tech.com/open-source/#bacnet-sim"><b>Website</b></a> · <a href="https://smartedge-tech-dev.github.io/sme-bacnet-sim/"><b>Docs</b></a> · <a href="https://github.com/smartedge-tech-dev/sme-bacnet-sim/releases/latest"><b>Download</b></a></p>

<p align="center"><a href="https://github.com/smartedge-tech-dev/sme-bacnet-sim/actions/workflows/ci.yml"><img src="https://github.com/smartedge-tech-dev/sme-bacnet-sim/actions/workflows/ci.yml/badge.svg" alt="CI"></a> <a href="https://github.com/smartedge-tech-dev/sme-bacnet-sim/releases/latest"><img src="https://img.shields.io/github/v/release/smartedge-tech-dev/sme-bacnet-sim" alt="release"></a> <a href="https://github.com/smartedge-tech-dev/sme-bacnet-sim/blob/main/LICENSE"><img src="https://img.shields.io/badge/license-MIT-5b5bd6" alt="license MIT"></a> <img src="https://img.shields.io/badge/platform-Windows%20%7C%20Linux%20%7C%20Docker-0a7bbb" alt="platform"> <img src="https://img.shields.io/badge/python-3.11%2B-3776ab" alt="python 3.11+"></p>

<p align="center"><strong>English</strong> | <a href="README.ja.md">日本語</a> | <a href="README.zh-CN.md">简体中文</a></p>

<p align="center"><img src="https://raw.githubusercontent.com/smartedge-tech-dev/sme-bacnet-sim/main/docs/assets/screenshots/en/live.gif" alt="Live point values and trend chart" width="100%"></p>

A BACnet/IP device simulator with a live web UI. Simulate lighting controllers, air conditioners, AHUs,
power meters, sensors, PV inverters — or any device you describe in YAML — and watch their values change
in the browser while a real BACnet client (Yabe, Niagara, your own EMS…) reads and commands them.

- **Many devices on one port.** A built-in BACnet router owns UDP 47808; every simulated device sits on a
  virtual network behind it (default network 100), so clients discover them all with one Who-Is.
- **Realistic behavior.** Room temperature follows the set point when the AC is on, energy integrates power,
  lights report feedback and power, PV output follows a day curve and respects a curtailment limit.
- **Real BACnet semantics.** Commandable outputs with a 16-level priority array and relinquish,
  out-of-service override, COV increments, Device / Network Port objects.
- **Configurable.** Import / export YAML or JSON, edit any device as YAML in the browser, add devices from
  templates, or save back to the config file.
- **Live UI.** Values stream over WebSocket, trend chart per point, event log of BACnet and UI writes.
- **English, Japanese and Simplified Chinese.** The UI follows the browser language; switch it under
  View → Language.

Built on [bacpypes3](https://github.com/JoelBender/BACpypes3) (asyncio BACnet stack, supports BACnet/IP,
IPv6 and BACnet/SC) and FastAPI. No front-end build step.

SME BACnetSim is free and MIT-licensed, developed by [smart-edge (智届科技)](https://smartedge-tech.com) —
custom development is available, see [Commercial support & custom development](#commercial-support--custom-development).

## Screenshots

<table>
  <tr>
    <td width="50%"><a href="https://raw.githubusercontent.com/smartedge-tech-dev/sme-bacnet-sim/main/docs/assets/screenshots/en/objects.png"><img src="https://raw.githubusercontent.com/smartedge-tech-dev/sme-bacnet-sim/main/docs/assets/screenshots/en/objects.png" alt="Event enrollment in alarm, notification class, life safety points"></a><br><sub>Event enrollment in alarm, notification class, life safety points</sub></td>
    <td width="50%"><a href="https://raw.githubusercontent.com/smartedge-tech-dev/sme-bacnet-sim/main/docs/assets/screenshots/en/custom-device.png"><img src="https://raw.githubusercontent.com/smartedge-tech-dev/sme-bacnet-sim/main/docs/assets/screenshots/en/custom-device.png" alt="A device built from scratch in YAML (expression and follow behaviors)"></a><br><sub>A device built from scratch in YAML (expression and follow behaviors)</sub></td>
  </tr>
  <tr>
    <td width="50%"><a href="https://raw.githubusercontent.com/smartedge-tech-dev/sme-bacnet-sim/main/docs/assets/screenshots/en/alarms.png"><img src="https://raw.githubusercontent.com/smartedge-tech-dev/sme-bacnet-sim/main/docs/assets/screenshots/en/alarms.png" alt="Alarm list with acknowledge"></a><br><sub>Alarm list with acknowledge</sub></td>
    <td width="50%"><a href="https://raw.githubusercontent.com/smartedge-tech-dev/sme-bacnet-sim/main/docs/assets/screenshots/en/properties.png"><img src="https://raw.githubusercontent.com/smartedge-tech-dev/sme-bacnet-sim/main/docs/assets/screenshots/en/properties.png" alt="Property inspector: read and write any property"></a><br><sub>Property inspector: read and write any property</sub></td>
  </tr>
  <tr>
    <td width="50%"><a href="https://raw.githubusercontent.com/smartedge-tech-dev/sme-bacnet-sim/main/docs/assets/screenshots/en/network.png"><img src="https://raw.githubusercontent.com/smartedge-tech-dev/sme-bacnet-sim/main/docs/assets/screenshots/en/network.png" alt="BACnet network settings, applied without a restart"></a><br><sub>BACnet network settings, applied without a restart</sub></td>
    <td width="50%"><a href="https://raw.githubusercontent.com/smartedge-tech-dev/sme-bacnet-sim/main/docs/assets/screenshots/en/overview-dark.png"><img src="https://raw.githubusercontent.com/smartedge-tech-dev/sme-bacnet-sim/main/docs/assets/screenshots/en/overview-dark.png" alt="Dark theme"></a><br><sub>Dark theme</sub></td>
  </tr>
</table>

## Quick start

```powershell
python -m venv .venv
.venv\Scripts\pip install -r requirements.txt
.venv\Scripts\python -m sme_bacnet_sim --config configs/demo-building.yaml
```

Open http://127.0.0.1:8080/ . Options:

| Option | Meaning |
|---|---|
| `-c, --config FILE` | YAML/JSON config (defaults to `configs/demo-building.yaml`) |
| `--ip 192.168.1.10/24` | NIC address for BACnet/IP (default: auto-detect, /24) |
| `--bacnet-port 47808` | BACnet/IP UDP port |
| `--foreign-bbmd 192.168.2.1[:47808]` | Register as a foreign device with this BBMD (overrides config) |
| `--foreign-ttl 300` | Foreign device Time-to-Live in seconds (overrides config) |
| `--host 0.0.0.0 --http-port 8080` | Web UI bind address (default localhost only) |
| `--browser` | Open the web UI in a browser on start (not opened by default; `--no-browser` is the default) |

### Connecting a BACnet client

The client sees the router (`device 4194000`) at `<ip>:47808` and the simulated devices at addresses such as
`100:1`, `100:2` (network 100, MAC 1, 2…) routed through it. In Yabe: *Add device → BACnet/IP over UDP*,
then *Who-Is*.

> **Same PC caveat:** on Windows, a client on the same machine may not receive broadcast replies
> (Who-Is/I-Am) — unicast works. Run the client on another machine, bind the simulator to a different NIC
> than the client, or set `network.mode: bbmd` and register the client as a foreign device.

> **Client on another UDP port:** Who-Is / I-Am broadcasts go to the simulator's port (47808 by default). A client
> bound to another port (e.g. 47809) does not receive the I-Am broadcasts and finds no devices. Either use the same
> port on both sides, or set `network.mode: bbmd` and register the client as a foreign device with the simulator
> (`<simulator ip>:47808`); the I-Am replies are then forwarded to the client.

### Network settings in the web UI

*Edit → BACnet network…* (or a click on the BACnet/IP address in the status bar) changes the network adapter
(listed by name and address/prefix, or *Auto-detect*), the UDP port, the IP-side and virtual network numbers, the
router device ID and the mode (normal / BBMD / foreign device with BBMD address and TTL). *Apply* checks the settings
(an address of this computer, a free UDP port, different network numbers, unique device IDs), rebinds BACnet/IP
without restarting and writes the `network:` section back to the config file (other sections and unsaved edits are
left as they are; comments inside `network:` are lost). Command-line options such as `--ip` / `--bacnet-port` still
win at the next start. Clients have to discover the devices again after a change.
Not supported: switching off Read-Property-Multiple or segmentation support (always on).

### Docker

```bash
docker run --rm --network host -e TZ=Asia/Tokyo ghcr.io/smartedge-tech-dev/sme-bacnet-sim:<ver>
```

`--network host` (Linux) is needed for Who-Is / I-Am broadcasts. Without `TZ` the container clock is UTC, and
schedules and the clock in the UI follow it (the image includes tzdata).

### Foreign device registration (cross-subnet)

To reach clients on another subnet, the router port can register as a foreign device with an existing BBMD:
`network.foreign_device: {bbmd: "<ipv4>[:port]", ttl: <seconds>}` or `--foreign-bbmd` / `--foreign-ttl`
(the command line wins; TTL defaults to 300 s, port to 47808). The registration uses bacpypes3's foreign
link layer: it is renewed every TTL, retried while unanswered, and cancelled (TTL 0) on stop or reload. Results
(registered / NAK / no answer within 10 s / expired) are written to the event log and shown in the status bar as
`FD → <bbmd> (…)`; the snapshot API reports them in `network.foreign_device`.

Not supported: combining `foreign_device` with `mode: bbmd`, BBMD host names (IPv4 literals only), and reading
or editing the BBMD's tables (Read-Broadcast-Distribution-Table, Read-Foreign-Device-Table and similar).

## Configuration

```yaml
network:
  ip: auto                # or "192.168.1.10/24"
  port: 47808
  network_number: 1       # IP-side network number
  virtual_network: 100    # network number of the simulated devices
  mode: normal            # or bbmd
  # foreign_device: {bbmd: "192.168.2.1:47808", ttl: 300}   # register with an external BBMD
  router: {device_id: 4194000, name: SME-BACnetSim-Router}

simulation:
  tick_seconds: 1.0
  time_scale: 1.0         # 60 = 1 simulated minute per second
  history_size: 600       # trend samples kept per point

devices:
  - device_id: 1002
    name: AC-1F-East
    template: split_ac             # optional
    params: {rated_kw: 2.8}        # template parameters
    objects:                       # add objects, or override template objects by name
      - {name: SetPoint, type: av, value: 24.0, commandable: true}
```

### Objects

| Key | Notes |
|---|---|
| `type` | `ai ao av bi bo bv msi mso msv acc pc loop file prog tl sch cal nc ee` (or full names such as `analog-input`, `trend-log`, `schedule`, `calendar`, `notification-class`, `event-enrollment`) |
| `instance` | optional; auto-numbered per type |
| `name`, `description` | `name` is also the variable name in expressions |
| `units` | BACnet engineering units, e.g. `degrees-celsius`, `kilowatts`, `percent` |
| `value` | initial value (binary: 0/1, multi-state: 1-based index) |
| `states` | multi-state texts |
| `active_text`, `inactive_text` | binary texts (quote `"ON"`/`"OFF"` — YAML reads them as booleans) |
| `commandable` | for `av/bv/msv`; outputs are always commandable |
| `min`, `max`, `cov_increment` | analog limits and COV increment |
| `behavior` | how the value is simulated (below) |
| `log_object`, `log_property`, `log_interval`, `logging_type`, `client_cov_increment`, `buffer_size`, `enabled` | trend logs only (below) |
| `weekly`, `exceptions`, `default`, `targets`, `priority_for_writing`, `effective_period` | schedules only (below) |
| `dates` | calendars only (below) |
| `scale`, `prescale` | accumulators only (below) |
| `scale_factor`, `input_object` | pulse converters only (below) |
| `controlled_object`, `manipulated_object`, `setpoint`, `setpoint_object`, `proportional_constant`, `integral_constant`, `derivative_constant`, `bias`, `action`, `update_interval` | loops only (below) |
| `file_type`, `access`, `content`, `path`, `read_only`, `program_state`, `instance_of`, `program_location` | files and programs only (below) |
| `monitored_object`, `event_type`, `event_parameters`, `notification_class`, `event_enable`, `notify_type`, `time_delay`, `time_delay_normal` | event enrollments only (below) |

#### Accumulators, pulse converters and loops

```yaml
- {type: acc, name: EnergyPulses, units: kilowatt-hours, scale: 0.01, max: 99999999,
   behavior: {type: pulse, rate: "ActivePower * 100 / 3600"}}
- {type: pc, name: EnergyFromPulses, input_object: EnergyPulses, scale_factor: 0.01, units: kilowatt-hours}
- type: loop
  name: SupplyTempLoop
  controlled_object: SupplyTemp      # controlled-variable-reference (present-value)
  manipulated_object: CoolValve      # manipulated-variable-reference (present-value)
  setpoint_object: SupplyTempSP      # or a fixed setpoint: 16
  proportional_constant: 8
  integral_constant: 0.2
  min: 0                             # minimum-output
  max: 100                           # maximum-output
  units: percent                     # output-units
  priority_for_writing: 10
```

| Type | Keys |
|---|---|
| `acc` (Accumulator, 23) | `value` (unsigned count), `units`, `scale` (Scale as a float scale, default 1), `max` (Max_Pres_Value, default 4294967295; above it the count wraps to 0), `prescale` (`[multiplier, modulo_divide]`) |
| `pc` (Pulse Converter, 24) | `value`, `units`, `scale_factor` (default 1), `input_object` (an accumulator of the same device → Input_Reference), `cov_increment` |
| `loop` (Loop, 12) | `controlled_object`, `manipulated_object`, `setpoint` or `setpoint_object`, `proportional_constant` (default 1), `integral_constant` (1/s, default 0), `derivative_constant` (s, default 0), `bias` (default 0), `action` (`direct` / `reverse`, default `direct`), `update_interval` (sim seconds, default 1; the Update_Interval property is in ms), `min` / `max` (output limits, default 0 / 100), `units` (Output_Units), `priority_for_writing` (default 16), `cov_increment` |

- **Accumulator**: driven by any behavior; the `pulse` behavior adds `rate` pulses per second.
- **Pulse converter** with `input_object`: every tick the accumulator's count delta (wrap-around included)
  times Scale_Factor is added to Present_Value, and Count shows the accumulator's count. Without
  `input_object` it is a plain Real value object (behaviors apply).
- **Loop** (textbook PID, on the simulated clock every Update_Interval): `e = PV − setpoint` (direct) or
  `setpoint − PV` (reverse); `output = bias + Kp·e + Ki·∫e dt + Kd·de/dt`, clamped to Minimum_Output ..
  Maximum_Output, with the integral held while the output is saturated (anti-windup). The output goes to the
  loop's Present_Value and to the manipulated object (its priority array at Priority_For_Writing when it is
  commandable, else its present value). Constants, setpoint, action, limits, update interval and write
  priority can be changed with WriteProperty. With a `setpoint_object`, Setpoint follows that object's value.
  Out of service: no computation and no output write. The UI shows the output plus PV / SP.
- **COV**: pulse converters use the COV-increment criteria, loops the generic criteria (present-value /
  status-flags), as defined by bacpypes3. bacpypes3 has no COV criteria for the Accumulator, so SubscribeCOV
  on an accumulator is not available (SubscribeCOVProperty works).
- **CreateObject** creates accumulators and pulse converters (without input reference); loops are declared
  in the config only. **DeleteObject** refuses objects referenced by a pulse converter or loop.
- **EDE**: accumulators and pulse converters are exported (unit code; the `max` column of an accumulator is
  Max_Pres_Value) and imported; loops are exported but skipped on import with a warning (EDE carries no
  references / PID constants).

Not supported: applying Prescale (stored only), Value_Set / Value_Before_Change / Value_Change_Time /
Logging_Record / Pulse_Rate and limit monitoring of the Accumulator; the Adjust_Value semantics of the
Pulse Converter (it is a plain writable property: Count and Present_Value are not adjusted),
Count_Before_Change / Count_Change_Time / Update_Time and COV_Period periodic notifications; intrinsic
reporting on these three types (`alarm` is rejected); references to other devices or to properties other
than Present_Value.

#### Files and programs

```yaml
- {type: program, name: AHU-Sequence, instance_of: AHU-Seq-v2, program_state: running}
- type: file
  name: MaintenanceLog
  file_type: text/plain            # File_Type (MIME type)
  access: record                   # stream (default) | record
  content: |-                      # or: path: logs/maintenance.txt (relative to the config file)
    2026-04-01 filter replaced
    2026-10-01 belt tension checked
- {type: file, name: Firmware, file_type: application/octet-stream, path: fw.bin, read_only: true}
```

| Type | Keys |
|---|---|
| `file` (File, 10) | `file_type` (default `text/plain`), `access` (`stream` / `record`), `content` (text) or `path` (file loaded at start, relative to the config file), `read_only` (default false) |
| `program` (Program, 16) | `program_state` (initial `idle` / `running` / `halted`, default `idle`), `instance_of` (default the object name), `program_location` |

File content is held in memory. Stream access works on the bytes; record access makes every line one record
(without the line terminator). File_Size is the byte count (record access: the sum of the record lengths) and
Record_Count the number of records. **AtomicReadFile / AtomicWriteFile** support both access methods: a start
position / record `-1` appends, a start beyond the end answers `services / invalid-file-start-position`, the
wrong access method `invalid-file-access-method`, a Read_Only file `file-access-denied`, a non-File object
`inconsistent-object-type` and a missing object `object / unknown-object`. A write updates File_Size /
Record_Count and Modification_Date (simulated clock). Written content of a `content` file is kept in the config,
so **Save** / Export store it (only when it is valid UTF-8); a `path` file is changed in memory only, the file
on disk is never written. File_Size, Modification_Date, File_Access_Method, Record_Count and Read_Only are
read-only for clients (`write-access-denied`).

Program: writing Program_Change applies the request at once and sets it back to `ready`: `load`, `run` and
`restart` -> `running`, `halt` -> `halted` (Reason_For_Halt `normal`, Description_Of_Halt "halted by request"),
`unload` -> `idle`, `ready` -> no change. Every request is accepted in every state. The UI shows the state and
a Program_Change menu (`POST /api/devices/{id}/program/{instance}/change`). Program_State, Reason_For_Halt,
Description_Of_Halt and Instance_Of are read-only for clients.

EDE carries no file content, file type or access method: imported files are empty stream files (with a
warning); programs are imported with their name.

Not supported: the transitional states `loading`, `waiting` and `unloading`, rejecting requests that are not
valid in the current state, any real program execution or failure (Reason_For_Halt other than `normal`),
writing File_Size to truncate a file, the Archive semantics (plain writable flag) and a consistency check of
the request's Record_Count against the records sent; the exact rules exist only in the paid ASHRAE 135 text.

#### Trend logs

`type: tl` (or `trend-log`) creates a BACnet Trend Log object that logs another object of the **same
device** (polled or on change) and keeps the samples in a ring buffer (oldest records are dropped,
`stop-when-full` is false):

```yaml
- {type: tl, name: RoomTemp_Log, log_object: RoomTemp, log_interval: 60, buffer_size: 1000}
- {type: tl, name: RoomTemp_Cov, log_object: RoomTemp, logging_type: cov, client_cov_increment: 0.5}
```

| Key | Default | Notes |
|---|---|---|
| `log_object` | (required) | name of the logged object; must exist in the device |
| `log_property` | `present-value` | any numeric / enumerated / boolean property of the target |
| `log_interval` | `60` | **simulated** seconds (BACnet `log-interval` is reported in 1/100 s); polled mode only |
| `logging_type` | `polled` | `polled` or `cov` (BACnet `logging-type`) |
| `client_cov_increment` | target's `cov-increment` | `cov` mode only; minimum change of a real value that is logged |
| `buffer_size` | `1000` | ring buffer size |
| `enabled` | `true` | initial value of the `enable` property (also writable over BACnet and from the UI) |

Samples are taken on the simulated clock and time-stamped with the simulated date/time, so with
`time_scale: 3600` an hour of real time yields a day of history at the configured interval. When one tick
is longer than `log_interval`, the missed intervals collapse into one sample. Read the buffer with
**ReadRange** (by position, by sequence number, by time, or without a range for everything that fits in
the response); `log-buffer` is not readable with ReadProperty. Writing `0` to `record-count` clears the log.
The `split_ac` and `power_meter` templates include one trend log each. EDE export / import carries trend logs
(see EDE below).

**COV logging** (`logging_type: cov`): instead of sampling on an interval, a record is appended whenever the
logged value has changed since the last record by at least the increment — `client_cov_increment` if set
(read back as `client-cov-increment`), else the target's `cov-increment` when logging its present value, else
any change; boolean / enumerated / integer values log on any change — or when the target's status flags
change. The first record is taken as soon as the log is enabled with an empty buffer (also after clearing).
Changes are detected once per simulation tick and stamped with the simulated clock; `log-interval` reads 0.
Not supported: the `triggered` logging type, logging objects of other devices (and therefore COV
subscriptions to them / `cov-resubscription-interval`), and log-status / time-change records in the buffer.

#### Schedules and calendars

`type: sch` (or `schedule`) creates a BACnet Schedule object that writes its value to objects of the
same device or of **another simulated device**; `type: cal` (or `calendar`) creates a Calendar object whose `present-value` is true on
the listed dates.

```yaml
- {type: cal, name: Holidays, dates: ["2026-12-25", {from: "2026-12-29", to: "2027-01-03"}, "*-01-01"]}
- type: sch
  name: Light_Sch
  targets:                      # written via list-of-object-property-references
    - Zone1_Cmd                 # object of this device
    - {device: AHU-1, object: Fan_Cmd}            # object of another simulated device (name or device id)
    - {device: 300100, object: "binary-value:4"}  # device outside the simulator: listed, never written
  priority_for_writing: 16
  default: "OFF"                # schedule-default
  weekly:
    weekdays: [{time: "08:00", value: "ON"}, {time: "18:00", value: "OFF"}]
    sat: [{time: "09:00", value: "ON"}, {time: "12:00", value: null}]   # null = back to default
  exceptions:
    - {calendar: Holidays, priority: 10, times: [{time: "00:00", value: "OFF"}]}
    - {date: "2026-11-03", priority: 5, times: [{time: "10:00", value: "ON"}]}
    - {date: {from: "2026-08-10", to: "2026-08-14"}, priority: 6, times: [{time: "00:00", value: "OFF"}]}
    - {date: {weeknday: ["*", 6, 5]}, priority: 8, times: [{time: "13:00", value: "OFF"}]}  # last Friday
  effective_period: {from: "2026-01-01", to: "2027-12-31"}   # optional, default always
```

| Key | Default | Notes |
|---|---|---|
| `weekly` | — | keys `mon`..`sun`, or `weekdays` / `weekend` / `daily`; each a list of `{time: "HH:MM[:SS]", value}` |
| `exceptions` | — | special events: one of `date` (same forms as calendar `dates`: `YYYY-MM-DD` with `*` wildcards, a `{from, to}` range or `{weeknday: [...]}`) or `calendar` (calendar object name), `priority` 1–16 (1 wins), `times` |
| `default` | 0 / `OFF` / 1 | schedule-default; at least one of `weekly` / `exceptions` is required |
| `targets` | none | output or value objects, all of the same kind: a name (this device) or `{device, object}`; `device` is a simulated device's name or id, `object` a name or `type:instance` (`av:3`, `binary-output:1`). A device id not in the simulator needs `object: type:instance`; it appears in `list-of-object-property-references` with its `deviceIdentifier`, is skipped (logged once at start) and never written over the network |
| `priority_for_writing` | `16` | priority-array slot used for commandable targets |
| `effective_period` | always | `{from, to}`; outside it the schedule keeps its value and writes nothing |
| `dates` (calendar) | `[]` | dates, `{from, to}` ranges, or `{weeknday: [month, week-of-month, day-of-week]}` (`*` = any; month 13 / 14 = odd / even months; week 1–5 = days 1–7 … 29–31, 6 = last 7 days of the month, 7–9 = the 7-day blocks before that; day 1 = Monday) |

The value type follows the targets: analog → REAL, binary → ENUMERATED (`0/1`, `true/false`, `ON/OFF`,
`active/inactive` or the target's texts), multi-state → UNSIGNED state number. Without targets the
values are REAL. Quote times (`"18:00"`): unquoted, YAML 1.1 reads `18:00` as the number 1080 (it is
still understood, but quoting is clearer).

Schedules run on the **simulated clock**, so `time_scale` fast-forwards them. bacpypes3's own schedule
interpreter uses the wall clock and asyncio timers, so the simulator keeps its Schedule object and
evaluation rules but re-evaluates every tick from the simulated date/time. When the value changes, or a
time entry of the weekly / exception schedule is reached (even with the same value, so a scheduled action
overrides operator changes), the schedule's `present-value` is set and the value is written to each target
at `priority_for_writing` (non-commandable value objects get `present-value` directly); between scheduled
actions nothing is written. A relinquish from a client therefore works normally; the schedule writes again
at its next time entry. Targets in other simulated devices are written directly into that device's object.
A ReinitializeDevice of a target's device re-commands the scheduled value; COV subscriptions are kept. `weekly-schedule`, `exception-schedule` and
`schedule-default` are writable over BACnet and take effect on the next tick (values of the wrong type set
`reliability` to `configuration-error`); exception entries may use dates, date ranges, weekNDay or
calendar references. The written content is kept in the config (Save / Export) as `weekly` / `exceptions` / `default` (binary values as 0 / 1, only the changed keys are rewritten; for a template schedule as an override entry); content the config cannot hold (wrong datatype, a calendar reference that is not a calendar of this device, a value the targets do not accept) is not kept and the config keeps the last valid content. `exception-schedule` is an array, so Add/RemoveListElement answers `property-is-not-a-list`. Calendar `date-list` is writable, too, and writing `list-of-object-property-references` changes the targets (present-value of output / value objects of the schedule's kind on this or another simulated device, or of a device outside the simulator; anything else is `value-out-of-range`); both are kept in the config (Save / Export). A client write to the schedule's own
`present-value` (with the schedule datatype, otherwise `invalid-data-type`) is forwarded to all targets at
`priority_for_writing` and holds until the next scheduled time entry; it is accepted whether or not
`out-of-service` is set.

Not supported: writing to targets on devices outside the simulator (no network WriteProperty).

The `lighting` template has a schedule switching `Zone1_Cmd` (weekdays 08:00 on, 18:00 off) and the
`split_ac` template one for `OnOff` (weekdays 09:00–18:00); disable them with the template parameter
`schedule: false`. The UI lists schedules and calendars with their current value and next transition;
click a row for the weekly / exception table. EDE export lists them as object types 17 / 6; EDE import
skips them.

#### Alarms (intrinsic reporting)

`type: nc` (or `notification-class`) creates a Notification Class object; its `instance` is the
notification class number. The web UI lists notification classes in the device's object list (read-only:
priorities, ack-required flags and recipients; edit them in the configuration).

| key | meaning |
|---|---|
| `priority` | `[to-offnormal, to-fault, to-normal]`, default `[100, 100, 200]` |
| `ack_required` | 3 flags, default `[true, true, false]` |
| `recipients` | list of `{device: <id>` and/or `address: "<net>:<mac>" \| "<ip>:<port>", process_id, confirmed, transitions: [3 flags], from_time, to_time, days}` |

A recipient given only by `device` is resolved with Who-Is (another simulated device directly; otherwise
the Who-Is goes out through the router, so the recipient must listen on the simulator's UDP port, usually a
BMS on another host). An `address` (`"<ip>:<port>"` means a station on the BACnet/IP side) skips the lookup.

Any value object can carry an `alarm` block that enables intrinsic reporting:

```yaml
- type: ai
  name: RoomTemp
  alarm: {notification_class: NC1, high_limit: 30, low_limit: 15, deadband: 0.5, time_delay: 60}
- {type: bi, name: FilterAlarm, alarm: {notification_class: 1, alarm_value: active}}
- {type: msi, name: Status, states: [Stopped, Running, Fault], alarm: {notification_class: 1, fault_values: [Fault]}}
```

| key | meaning |
|---|---|
| `notification_class` | name or instance of a notification-class object in the same device |
| `high_limit`, `low_limit`, `deadband`, `limit_enable` | analog (OUT_OF_RANGE); `limit_enable` `[low, high]` defaults to the limits that are set |
| `alarm_value` | binary (CHANGE_OF_STATE): `active` / `inactive` |
| `alarm_values`, `fault_values` | multi-state: state numbers or texts; a fault value puts the object in `fault` |
| `time_delay`, `time_delay_normal` | **simulated** seconds (default 0 / `time_delay`) |
| `event_enable` | `[to-offnormal, to-fault, to-normal]`, default all true |
| `notify_type` | `alarm` (default) or `event` |

Event states are evaluated on the simulated clock (time delays follow the speed and stop while paused;
writes are evaluated immediately). Transitions update Event_State, Event_Time_Stamps, Acked_Transitions and
the in-alarm status flag, are sent as Confirmed / UnconfirmedEventNotification to the recipients, and appear
in the event log. The simulator answers AcknowledgeAlarm, GetEventInformation, GetAlarmSummary and
GetEnrollmentSummary (all filters, including the enrollment filter = recipient + process identifier of the
object's notification class); the web UI shows an alarm badge per row, an
**Ack** button, the active-alarm count in the header and *View → Alarms*. The `split_ac`, `ahu` and
`power_meter` templates add `NC1` (no recipients) and a few alarms; set the template parameter
`alarms: false` to leave them out. `split_ac`'s RoomTemp high limit (template parameter `high_limit`,
default 35 °C) is an overheat alarm above the template's ambient peak (33 °C), so the demo starts and runs
without alarms while the ACs follow their schedules; to see one, write `high-limit` (e.g. 28) from a client.

BACnet writes (WriteProperty / WritePropertyMultiple) to `event-enable`, `limit-enable`, `high-limit`,
`low-limit`, `deadband`, `time-delay`, `time-delay-normal`, `notification-class` (must be a notification-class
object of the device) and `alarm-value` / `alarm-values` take effect and are written into the config, so
Save / Export keep them. `acked-transitions` is read-only (WriteProperty answers `write-access-denied`).

WritePropertyMultiple validates every item first (object exists, property exists, array index, datatype, the
alarm property rules above, Priority_Array of commandable objects) and writes nothing if one fails; the
error names the first failing object / property. Value checks done only inside an object's own write hook
(e.g. trend log / schedule range checks) still run while writing, so such a failure can leave the earlier
items of the request applied.

bacpypes3 0.1.0 cannot decode a GetAlarmSummary / GetEnrollmentSummary ACK whose list is empty (a filter
that matches nothing) and reports it as `invalid-tag`; the simulator itself encodes the empty ACK correctly
and patches the decoder for bacpypes3 clients running in the same process (`sme_bacnet_sim/alarm.py`).
Other bacpypes3 0.1.0 clients see the same error until they apply the same fix.
A multi-state object that is already `offnormal` and changes to a different alarm value makes a new
`offnormal -> offnormal` transition (and notification) after `time_delay`.

Limitations: bacpypes3's own intrinsic-reporting algorithms run on the wall clock, so the simulator uses its
own (see `sme_bacnet_sim/alarm.py`).

Not supported: acknowledgment notifications (notify type `ack-notification`). AcknowledgeAlarm is answered and
updates Acked_Transitions, but no notification is sent to recipients. Exact all-or-nothing semantics of
WritePropertyMultiple beyond the up-front validation above (rollback of already applied writes). SME BACnetSim is free and is built from
public sources only; behaviors that can only be specified from the paid ASHRAE 135 text are left out.

#### Event enrollments (algorithmic reporting)

`type: ee` (or `event-enrollment`) creates an Event Enrollment object that monitors the present-value of
another value object of the same device and reports through a notification class, so a point without an
`alarm` block (e.g. a template's temperature) can still raise alarms:

```yaml
- type: ee
  name: RoomTempWatch
  monitored_object: Temperature
  event_type: out-of-range
  event_parameters: {low_limit: 18, high_limit: 28, deadband: 0.5}
  notification_class: RoomAlarms
  time_delay: 60
- {type: ee, name: ModeWatch, monitored_object: OperationMode, event_type: change-of-state,
   event_parameters: {alarm_values: [Maintenance]}, notification_class: 1, notify_type: event}
```

| key | meaning |
|---|---|
| `monitored_object` | name of a value object of the same device (Object_Property_Reference = its present-value) |
| `event_type` | `out-of-range` (analog, accumulator excluded) or `change-of-state` (binary / multi-state) |
| `event_parameters` | out-of-range: `low_limit`, `high_limit` (both required, both always enabled), `deadband`; change-of-state: `alarm_values` (state numbers or texts, `active` / `inactive` for binary) |
| `notification_class` | name or instance of a notification-class object in the same device |
| `time_delay`, `time_delay_normal` | **simulated** seconds (default 0 / `time_delay`); `time_delay` is the Time_Delay of Event_Parameters |
| `event_enable` | `[to-offnormal, to-fault, to-normal]`, default all true |
| `notify_type` | `alarm` (default) or `event` |

Event enrollments use the same event state machine, notifications, AcknowledgeAlarm,
GetEventInformation / GetAlarmSummary / GetEnrollmentSummary and web UI (row with badge and **Ack**,
*View → Alarms*) as intrinsic reporting. BACnet writes to `event-parameters` (same event type),
`event-enable`, `notify-type`, `time-delay-normal` and `notification-class` take effect and are written into
the config; `acked-transitions` is read-only. The demo configuration's `Room-Sensor-101` has one. EDE export
lists event enrollments (object type 9); EDE import skips them with a warning (EDE carries no monitored
object or parameters).

Not supported: the event types `floating-limit`, `change-of-value` and all others (their exact algorithms are
specified only in ASHRAE 135), fault detection of event enrollments (no `fault` state / change-of-reliability),
monitoring objects of other devices or properties other than present-value, changing `event-type` or
`object-property-reference` by a BACnet write, and creating / deleting event enrollments with
CreateObject / DeleteObject. A value object monitored by an event enrollment cannot be deleted.

#### Life safety points and zones

```yaml
      - {type: lsp, name: Smoke-101, description: Smoke detector}   # life-safety-point (object type 21)
      - type: lsp
        name: Heat-101
        value: quiet               # initial state (BACnetLifeSafetyState: quiet, pre-alarm, alarm, fault, ...)
        mode: "on"                 # BACnetLifeSafetyMode (default on; quote on / off in YAML)
        accepted_modes: ["on", "off", test]   # default [off, on, test]
        operation_expected: none   # BACnetLifeSafetyOperation, read-only (default none)
        silenced: unsilenced       # initial BACnetSilencedState
        behavior: {type: random_alarm, probability: 0.001, state: alarm}  # optional, per sim second
      - {type: lsz, name: Zone-101, zone_members: [Smoke-101, Heat-101]}  # life-safety-zone (object type 22)
```

The simulator uses a simplified model (the full state machine is only specified in ASHRAE 135):

- **Tracking_Value** is the live detector state. Set it from the UI (detector-state menu of the row,
  `POST /api/devices/{id}/life-safety/{type:instance}/state`) or with the optional `random_alarm` behavior
  (goes to `state` at random, back to `quiet` on the next tick). It is read-only for BACnet clients.
- **Present_Value** follows Tracking_Value while that is not `quiet` and stays **latched** when it returns to
  `quiet`, until a reset. BACnet writes to present-value are only accepted while out-of-service.
- **Zone**: its Tracking_Value is the present value of the first member (in Zone_Members order) that is not
  `quiet`, else `quiet`. This is a simplification: no severity order between the states is applied.
- **LifeSafetyOperation**: `silence` / `silence-audible` / `silence-visual` set and `unsilence*` clear the
  audible / visible part of Silenced; `reset` / `reset-alarm` / `reset-fault` (all the same here) copy
  Tracking_Value to Present_Value and unsilence; `none` does nothing. An operation on a zone also acts on its
  members; without an object identifier it acts on every life safety object of the device. Vendor-specific
  operations return `services` / `optional-functionality-not-supported`, other object types `object` /
  `unsupported-object-type`. Every operation is written to the event log.
- **Mode** is writable but must be one of accepted-modes (else `property` / `value-out-of-range`);
  **zone-members** is writable (WriteProperty, AddListElement / RemoveListElement) and written back to the
  config as member names (references to other devices are ignored).
- ReinitializeDevice restores the configured state. EDE export lists them (object type 21 / 22, state number
  as value); EDE import keeps type, name and state.

Not supported: change-of-life-safety event reporting (alarm-values, life-safety-alarm-values, fault-values and
the event properties are not evaluated), the severity order of the states and mode-dependent transitions,
maintenance-required / direct-reading / setting behaviour, and creating / deleting life safety objects with
CreateObject / DeleteObject.

### Device management services

Each simulated device also serves (bacpypes3 0.1.0 leaves most of these unimplemented or broken on the server
side, so the simulator implements them in `sme_bacnet_sim/engine.py` / `sme_bacnet_sim/devmgmt.py`):

- **COV increment default** (analog objects without `cov_increment`): a point with a `behavior` (it changes
  every tick) gets 1 % of its span (`min` / `max` of the object, else `min` / `max` of the behavior), else a
  per-unit default (0.1 for °C / kW / kWh / A, 0.5 for % / %RH / V / m³/h, 1 for W / Pa, 5 for ppm / lx / W/m²,
  0.01 Hz; see `_UNIT_COV` in `sme_bacnet_sim/engine.py`), else `0`; points without a behavior keep `0` (= any change).
  Set `cov_increment` explicitly to override.
- **SubscribeCOV** (confirmed / unconfirmed, with lifetime) on all value objects: a notification on a
  presentValue change of at least `covIncrement` (analog), whether it comes from a behavior, a BACnet write or the UI, and on any status-flags change
  (alarm, fault, out-of-service). **SubscribeCOVProperty** on any property, with the client's COV increment
  (default: the object's `covIncrement` for present-value); the notification carries the property and the
  status flags.
- **CreateObject / DeleteObject** for value objects (AI/AO/AV/BI/BO/BV/MSI/MSO/MSV, Accumulator, Pulse Converter), by object type (first free
  instance) or by object identifier, with optional initial values: object-name, present-value, description,
  units / cov-increment (analog), active-text / inactive-text (binary), state-text (multi-state, default
  `State 1`, `State 2`), out-of-service. A created object is appended to the device's `objects` in the
  running config (so Save / Export keep it) and appears in the UI at once. Deleting removes it from `objects`;
  if the object comes from a template its name is added to the device's `removed` list, which template
  expansion skips (remove the name from `removed` to get the template object back; creating an object with
  that name also drops it from `removed`). Not deletable (`object` / `object-deletion-not-permitted`): the
  device object, network ports, trend logs, schedules, calendars, notification classes, and value objects
  logged by a trend log or written by a schedule. Errors on create use CreateObject-Error with the failing
  element number (`dynamic-creation-not-supported`, `object-identifier-already-exists`, `duplicate-name`,
  `write-access-denied` for other properties, `invalid-data-type`).
- **TimeSynchronization / UTCTimeSynchronization** (to a device, or to the router / broadcast): moves the
  simulated clock so that it shows the received time (UTC is converted with the host's time zone); the
  elapsed simulated time keeps running, schedules are re-evaluated at once and trend logs continue on the new
  clock. *Simulation → Sync to PC clock* (or `POST /api/simulation {"set_time": ...}`) does the same from the UI.
- **DeviceCommunicationControl** enable / disable / disable-initiation with an optional time duration in
  minutes, measured on the **wall clock** (the duration is a real-world timeout in the standard, independent of
  the simulation speed). While disabled the device ignores everything except DeviceCommunicationControl and
  ReinitializeDevice and sends nothing (no I-Am, COV or event notifications); disable-initiation still answers
  requests and Who-Is but initiates nothing else. The device header in the UI shows the state with an
  *Enable communication* button.
- **ReinitializeDevice** warmstart: values back to the configured initial values, priority arrays
  relinquished, out-of-service cleared, behaviors and alarms (event state normal, all acknowledged) reset,
  communication re-enabled. Coldstart: the same, and trend-log buffers are cleared. Other states return
  `services` / `optional-functionality-not-supported`.

Device keys for these services:

```yaml
  - device_id: 1002
    name: AC-1F-East
    dcc_password: secret      # DeviceCommunicationControl password (default: none = not checked)
    reinit_password: boot     # ReinitializeDevice password (default: none = not checked)
    removed: [FilterAlarm]    # template objects deleted with DeleteObject (written by the simulator)
```

A wrong password returns `security` / `password-failure`.

### Text messages, private transfer and list element services

- **ConfirmedTextMessage / UnconfirmedTextMessage** received by a simulated device are written to the event
  log (kind `text-message`: sender address and device, priority, message class, text). A simulated device can
  send one with `POST /api/devices/{id}/text-message`
  `{"message": "...", "address": "100:2", "priority": "normal", "message_class": 5, "confirmed": false}`
  (`address` default: global broadcast `*:*`, which cannot be confirmed; `message_class` a number or text).
- **ConfirmedPrivateTransfer / UnconfirmedPrivateTransfer** are written to the event log (kind
  `private-transfer`). A confirmed request is answered as declared in the device's `private_transfer` list;
  `result: echo` (default) returns the service parameters as the result block, `null` no result block, a
  string / integer / real / boolean that value. Without a matching entry the answer is a
  ConfirmedPrivateTransfer-Error `services` / `optional-functionality-not-supported`: the device does support
  the service, only not that vendor / service number, so the simulator uses this error rather than a
  `unrecognized-service` reject (which would claim the whole service is missing).
- **AddListElement / RemoveListElement** on any writable list property (e.g. notification class
  recipient-list, calendar date-list, schedule list-of-object-property-references, life safety zone
  zone-members). Elements are decoded with the bacpypes3 property datatype; the new list is written exactly
  like a WriteProperty of the whole list (same checks and follow-ups). Elements already in the list are
  ignored on add. Errors (Add/RemoveListElement-Error): unknown object / property, `services` /
  `property-is-not-a-list` (property is not a list), `property` / `property-is-not-an-array` (array index
  given), `write-access-denied`, `invalid-data-type`, and `services` / `list-element-not-found` with the
  (1-based) number of the first element that is not in the list on remove. Written back to the config:
  zone-members, recipient-list (also used for sending notifications at once), date-list and
  list-of-object-property-references (the schedule writes to the new targets), as with WriteProperty; objects that
  come from a template are kept as an override entry.

```yaml
  - device_id: 1006
    name: Room-Sensor-101
    private_transfer:
      - {vendor_id: 999, service_number: 1}              # result: echo (default)
      - {vendor_id: 999, service_number: 2, result: 42}  # fixed value
```

Not supported: vendor-specific meaning of private transfer parameters (they are not decoded), text messages
from the router device, and the AddListElement / RemoveListElement rules that only ASHRAE 135 defines for
individual properties beyond the checks above.

### Behaviors

| `type` | Parameters | Example |
|---|---|---|
| `sine` | `min max period phase noise` | daily or periodic swings |
| `random` | `min max` | uniform noise |
| `random_walk` | `min max step` | drifting sensor |
| `expr` | `expr` | `"Zone1_Cmd"`, `"1.732 * Voltage * Current * PowerFactor / 1000"` |
| `follow` | `target tau noise` | first-order lag to a target: `"SetPoint if OnOff else 30"` |
| `counter` | `rate` | integrates units/second: `"Power / 3600"` → kWh |
| `pulse` | `rate` | accumulator pulses per second (fractions carried over): `"ActivePower * 100 / 3600"` |
| `replay` | `file column interpolate loop offset` | play a CSV time series (below) |

**CSV replay** (`replay`): the first CSV column is the timestamp — elapsed time (`HH:MM:SS` or seconds) or an
ISO datetime — and every other column is a value series. Each point names the `file` and its `column`, so one CSV
can drive many points (the file is parsed once). Relative paths resolve against the config file's directory.
Replay time 0 is the first row and advances with the simulated clock, so it follows `simulation.time_scale`.
`interpolate: linear` (default) or `step` (hold the previous row); binary and multi-state points always step-hold
(`active` / `inactive` / `1` / `0`, state numbers). `offset` starts mid-file (`"06:00:00"`, seconds, or an ISO
datetime for ISO CSVs); `loop: true` repeats, otherwise the last value is held. An empty cell holds the previous
value. Bad timestamps, rows going backwards or an unknown column are reported when the config is loaded. The
point row shows the replay position, e.g. `replay 06:12:30 (26%)`. Example: `configs/replay-example.yaml` with
`configs/data/day-profile.csv`:

```csv
time,oat,rh,occupied,mode
00:00:00,13.8,71,inactive,1
08:00:00,17.2,64,active,2
19:00:00,20.2,56,inactive,1
24:00:00,13.8,71,inactive,1
```

```yaml
- {type: ai, name: OutdoorTemp, units: degreesCelsius,
   behavior: {type: replay, file: data/day-profile.csv, column: oat, loop: true, offset: "06:00:00"}}
- {type: bi, name: Occupied,
   behavior: {type: replay, file: data/day-profile.csv, column: occupied, loop: true, offset: "06:00:00"}}
```

Expressions are sandboxed Python expressions. Available names: the device's object names, `t` (sim seconds),
`dt`, `hour` (sim clock, 0–24), `pv("Device", "Object")` to read another device, and
`sin cos exp log sqrt pi abs min max round clamp random uniform noise gauss`.

Objects that are **out of service** stop following their behavior, which is how you inject a fixed value or
a fault. Writing a simulated input from the UI sets it out of service automatically.

### Templates

`lighting`, `split_ac`, `ahu`, `power_meter`, `env_sensor`, `pv_inverter`, `custom` — see
[sme_bacnet_sim/templates.py](sme_bacnet_sim/templates.py). Adding your own is a ~20-line function.

### EDE import / export

SME BACnetSim reads and writes EDE files (B.I.G.-EU Engineering Data Exchange, layout 2.3), the CSV point list
most BACnet tools and integrators exchange.

- **Export**: the `EDE` button (`GET /api/config/export?format=ede`) downloads a zip with the main file
  `sme-bacnet-sim-ede.csv` (one row per object, plus one device row with object-type 8; numeric object-type and
  unit codes; templates expanded) and the state-text file `sme-bacnet-sim-ede-statetexts.csv`
  (binary objects: Text 1 = inactive, Text 2 = active; multi-state objects: states 1..N).
- **Import**: select the main CSV, optionally together with the state-text CSV (or the exported zip).
  The state-text file is recognised by its header. Semicolon or comma delimiters, UTF-8 (with or without
  BOM) and cp1252 are accepted. Rows are grouped into one device per device instance (name taken from the
  device row, else `Device-<id>`); `settable = Y` on AV/BV/MSV makes the object commandable. Object types
  the simulator does not support are skipped and reported as warnings in the event log. Network and
  simulation settings of the running config are kept; imported objects are static (no behaviors).
- **Trend logs** (object type 20): export writes the trend-log settings into the `vendor-specific-address`
  column as `key=value` pairs separated by `|` (e.g. `log_object=RoomTemp|log_interval=60|logging_type=cov`;
  keys as in YAML), so an exported file re-imports with its trend logs. Files from other tools carry no logged
  object reference; the import then logs `<name>` for a trend log named `<name>_Log` when that object exists,
  else the first analog / binary / multi-state object of the device (polled, 60 s), with a warning.
- **Accumulator / Pulse Converter / Loop** (object types 23 / 24 / 12): see Objects above.
- **hi-limit / low-limit** map to `alarm.high_limit` / `alarm.low_limit` of analog objects. On import the alarm
  uses the device's first notification class; if the file has none, `NC-1` (instance 1, no recipients) is
  created. Notification classes are imported with default priorities and no recipients (EDE has no columns for
  them). Other alarm settings (deadband, time delay, binary / multi-state alarm values) are not carried by EDE.

### Excel point list

File → **Download blank Excel template** (`GET /api/config/xlsx-template`) gives an empty `.xlsx` point list;
File → Export → **Excel point list** (`GET /api/config/xlsx`) writes the running config;
File → Import accepts the `.xlsx`. Sheets: `Devices` (one row per device: `device_id`, `name`, `template`,
`params`, vendor / location / passwords), `Points` (one row per object: `device_id`, `type`, `instance`, `name`,
`units`, `value`, `commandable`, `min` / `max`, `cov_increment`, `state_texts`, active / inactive text,
`behavior`, `alarm_class` / `alarm_high_limit` / `alarm_low_limit` / `alarm_deadband` / `alarm_values` /
`alarm_time_delay`), `StateTexts` (`ref`, `text_1..N`) and an optional `Network` sheet (`key` / `value`).
Column names are English; the row below the header is a `#` comment row with Japanese / Chinese descriptions.
Settings without a column go into the `extra` column as a YAML flow mapping, so export → import round-trips.
Import errors name the sheet, row and column (`Points row 12, column 'instance': not an integer`); warnings go to
the event log. Details: [docs/en/excel.md](docs/en/excel.md).

### Cloning real devices

`sme-bacnet-sim clone` reads real BACnet devices (read-only) and writes a simulator config, so later tests run
offline. Full reference: `docs/en/cloning.md`.

- **Get the customer's permission first**; prefer non-operating hours. Start with a small `--who-is` range and keep
  the default `--rate` (5 requests/s): MS/TP trunks and low-end controllers are easily loaded.
- **Read-only guarantee**: the clone client can only send Who-Is, ReadProperty and ReadPropertyMultiple (any other
  APDU is refused in code, a test asserts it) and never answers requests from other devices.
- **On a gateway (e.g. Moxa, ARM) use Docker** — `--network host` is required for Who-Is / I-Am:

  ```sh
  docker load -i sme-bacnet-sim-<ver>-linux-<arch>.tar.gz      # offline; or: docker pull ghcr.io/smartedge-tech-dev/sme-bacnet-sim:<ver>
  docker run --rm --network host --user "$(id -u):$(id -g)" -v "$PWD":/out \
    ghcr.io/smartedge-tech-dev/sme-bacnet-sim:<ver> sme-bacnet-sim clone --who-is 1000-1010 -o /out/site.yaml
  ```

  Images: `linux/amd64`, `linux/arm64`, `linux/arm/v7` (`uname -m` = `armv7l`, e.g. Moxa). Offline gateways: download
  `sme-bacnet-sim-<ver>-linux-<arch>.tar.gz` (`amd64` / `arm64` / `arm-v7`) from the GitHub Release, copy it over
  (e.g. FTP) and `docker load -i` it as is (no need to gunzip). See `docs/en/cloning.md`.

  With Python 3.10+: `pip install .` (venv or `pip install --user .`) from a checkout. The release only ships a
  PyInstaller executable for x86-64 Windows (no Linux / macOS / ARM executable).
- **Targets**: `--who-is LOW-HIGH` (local broadcast), `--address IP[:PORT]` (unicast; with `--devices ID` no Who-Is
  at all), `--network N` (with `--address`: the router to network N), `--devices ID,...`. One is required.
- **Across subnets**: `--foreign-bbmd HOST[:PORT]` (and `--foreign-ttl`) registers the client as a foreign device
  with a BBMD so the broadcast I-Am answers reach it, e.g. `clone --foreign-bbmd 192.168.251.8 --who-is 0-4194302`.
- **Other options**: `--ip`, `--port` (default 47808), `--client-device-id` (default 4194300), `--rate`,
  `--timeout`, `--retries`, `--no-rpm`, `--object-list-file` (object table for devices whose object-list cannot be
  read), `--no-keep-ids`, `--resume`, `-o OUT.yaml`.
- Object lists are read by array index (no segmentation needed); RPM falls back to ReadProperty; requests stay
  within the device's max-apdu. The YAML is rewritten after each device (Ctrl+C keeps what was read) and
  `OUT.yaml.log.jsonl` logs every request / answer / error / warning.
- Cloned: device info, all supported object types with names, units, state texts, COV increments, commandable,
  alarm parameters, notification classes, schedules, calendars, trend logs and the other supported objects'
  settings. Not cloned: file content, address recipients, references to other devices (warnings in the log).
- **Coexisting with another BACnet client** on the gateway (e.g. BAC0 on 47808): use `--port 47809`; I-Am answers
  may go to 47808, so use `--address <device IP> --devices <id>`; pick `--client-device-id` if 4194300 collides.
- **Offline**: when nothing can run on site, export EDE from the customer's tool and use the EDE import.
- **Recording values for replay**: `sme-bacnet-sim record` polls present-values (RPM with ReadProperty fallback) into a
  CSV for the `replay` behavior, and with `--trend-log` reads Trend Log buffers (ReadRange). Read-only like clone;
  stop with `--duration` / `--count` / Ctrl-C, `--resume` appends. See `docs/en/cloning.md`.

  ```sh
  sme-bacnet-sim record -c site.yaml --address 192.168.1.50 --interval 60 --duration 8h -o data/site.csv
  ```

### Copy / paste and the property grid

- **Devices**: *Copy* in the device header (or right-click a device in the list, or Ctrl+C with no point selected),
  then *Paste* (header button, *Edit → Paste* or Ctrl+V) adds a duplicate with the next free device ID after the
  source and the name `Name (copy)`. The duplicate is written to the configuration like *Add device*.
- **Points**: select rows with Ctrl / Shift click, Ctrl+C (or *Edit → Copy*), select a device (the same or another
  one) and Ctrl+V. Each pasted object gets the next free instance of its type and, on a name clash, a
  `(copy)` suffix. References (`log_object`, schedule `targets` / exception `calendar`, `input_object`, loop
  `*_object`, `monitored_object`, `notification_class`, `alarm.notification_class`) are kept by name; a reference
  to an object pasted in the same batch follows the renamed copy. When a referenced name does not exist in the
  target device the object is not pasted and the reason is shown and written to the event log.
  Ctrl+C / Ctrl+V only act while no text field or dialog has the focus; the clipboard lives in the page memory.
- **Properties**: the ⚙ button on a row (or *Properties* in the device header for the device object) lists every
  property of the BACnet object, ordered by property identifier, with value, datatype and whether it can be
  written. Writes take the same path as a BACnet WriteProperty request (same checks, alarm properties written
  back to the configuration); a commandable Present_Value is written at a chosen priority or relinquished.
  Only basic types (real, double, unsigned, integer, boolean, enumerated, character string) can be edited;
  constructed values (arrays, lists, sequences) are shown as JSON and are read-only in the UI. Object_Identifier,
  Object_Type and Property_List are never written from the UI.

## HTTP API

| Method | Path | |
|---|---|---|
| GET | `/api/version` | `{name, version, common_version}` |
| GET | `/api/state` | full snapshot |
| WS | `/ws` | snapshot + value changes + log events |
| POST | `/api/devices/{id}/objects/{type:instance}/write` | `{"value": 1, "priority": 8}` |
| POST | `.../relinquish`, `.../oos` | `{"priority": 8}`, `{"out_of_service": true}` |
| POST | `/api/devices/{id}/objects/{type:instance}/ack` | acknowledge all unacknowledged transitions of the object's alarm |
| POST | `/api/devices/{id}/dcc` | `{"state": "enable"}` (or `disable` / `disable-initiation`) |
| POST | `/api/simulation` | `{"running": true, "time_scale": 60, "set_time": "2026-11-23T08:00:00"}` (all optional; naive time = local) |
| GET/PUT | `/api/config` | whole config (PUT accepts YAML or JSON text) |
| POST | `/api/config/save` | write the running config to the `-c` file (400 if started without `-c`); returns `{ok, path}` |
| GET/PUT | `/api/network` | network settings + local IPv4 interfaces (`{network, bind, config_path, interfaces}`); PUT `{ip, port, network_number, virtual_network, mode, router, foreign_device}` validates, rebinds and writes the `network:` section back → `{ok, bind, saved, save_error}` |
| POST | `/api/config/import` | multipart upload: one YAML / JSON / Excel (`.xlsx`) file, or EDE CSV files / zip (field `file`, repeatable) |
| GET | `/api/config/export?format=yaml\|json\|ede` | download (`ede` = zip of main + state-text CSV; Excel: `GET /api/config/xlsx`) |
| GET | `/api/config/xlsx` | download the running config as an Excel point list |
| GET | `/api/config/xlsx-template` | blank Excel point-list template |
| GET | `/api/templates` | template catalog |
| POST | `/api/templates/reload` | reload user templates; returns `{dir, loaded, errors, templates}` |
| POST | `/api/templates/from-device/{id}` | `{"name": "my-ahu", "title": ..., "description": ..., "overwrite": false}` saves the device as a user template; returns `{ok, name, path}` (409 if it exists) |
| POST/PUT/DELETE | `/api/devices`, `/api/devices/{id}/config` | add / edit / delete device; POST `/api/devices` without `device_id` takes the first free ID from 1001 and returns `{ok, name, device}` (409 if the ID exists); `GET /api/devices/{id}/config` returns the device as YAML |
| POST | `/api/devices/{id}/duplicate` | copy of the device (optional `{"device_id"}`, else next free ID; name `Name (copy)`); returns `{ok, name, device}` (`name` = new device ID, `device` = the copy) |
| GET | `/api/devices/{id}/objects/config?keys=analog-value:1,...` | object configs (template objects expanded) for copying |
| POST | `/api/devices/{id}/objects/paste` | `{"objects": [object config, ...]}` → `{"pasted": [{name, key}], "rejected": [{name, reason}]}` |
| GET | `/api/devices/{id}/objects/{type:instance}/properties` | all properties (`device:{id}` = device object): `[{id, name, value, datatype, writable, editable, kind}]` |
| PUT | `/api/devices/{id}/objects/{type:instance}/properties/{property}` | `{"value": 21.5, "priority": 8}` (basic types only; `null` + priority relinquishes) |
| GET | `/api/history/{id}/{type:instance}` | trend samples |
| GET | `/api/devices/{id}/trendlog/{instance}` | trend-log buffer `[[timestamp, value], ...]` (simulated clock) |
| POST | `/api/devices/{id}/trendlog/{instance}/enable` | `{"enabled": true}` |
| POST | `/api/devices/{id}/program/{instance}/change` | `{"request": "halt"}` (load / run / halt / restart / unload / ready) |
| POST | `/api/devices/{id}/text-message` | `{"message": "...", "address": "100:2", "priority": "normal", "message_class": 5, "confirmed": false}` (address default: global broadcast) |
| POST | `/api/devices/{id}/life-safety/{type:instance}/state` | `{"state": "alarm"}` (Tracking_Value of a life safety point) |

## Development

```powershell
.venv\Scripts\pip install pytest
.venv\Scripts\python -m pytest -q
```

The end-to-end test starts the simulator on UDP 47900 and talks to it with a bacpypes3 client through the
router.

## Commercial support & custom development

SME BACnetSim is developed by **smart-edge** — Nanjing Smart-Edge Technology Co., Ltd. (南京智届科技有限公司, 智届科技).
Since its founding in 2023 the company has developed end-to-end software for distributed energy resources
such as solar, batteries and EVs, from equipment control to the cloud and electricity markets. Its products
include the AERIS RA platform (リソースアグリゲーター向け) and an AC system (アグリゲーションコーディネーター) for
the Japanese electricity markets. The team supports projects in Japanese, from requirements definition
through design, implementation, operation and maintenance.

Services:

- Energy management systems (EMS), cloud and on-site
- RA / AC systems for electricity markets (JEPX, EPRX, OCCTO)
- Edge IoT and equipment-control software
- Equipment integration: Modbus, MQTT, BACnet, ECHONET Lite, OpenADR 2.0b
- Energy forecasting and data analytics
- Cloud infrastructure design, build and operation

Need a feature added to SME BACnetSim, or help integrating your devices or EMS? Get in touch:

- Website: <https://smartedge-tech.com>
- Contact page: <https://smartedge-tech.com/contact/>
- E-mail: [business@smartedge-tech.com](mailto:business@smartedge-tech.com)

## License

[MIT](LICENSE)